File #: 22-773    Name: Support Request to Include 1322 Natividad Road, Emergency Communications (911) HVAC Project in FY 2022-23 CIP and Fund Project from Cannabis Tax Assignment
Type: General Agenda Item Status: Agenda Ready
File created: 9/12/2022 In control: Capital Improvement Committee
On agenda: 9/12/2022 Final action:
Title: a. Support a request to include the 1322 Natividad Road, Emergency Communications (911) Heating Ventilation and Air Conditioning Unit (HVAC) project into the fiscal year (FY) 2022-23 Capital Improvement Program; and b. Support the request to fund this project with funding from the Building Improvement and Replacement Sub-Fund (Fund 478-BIR, Appropriation Unit CAO047).
Attachments: 1. CIC Report, 2. Attachment A - Budget Sheet
Title
a. Support a request to include the 1322 Natividad Road, Emergency Communications (911) Heating Ventilation and Air Conditioning Unit (HVAC) project into the fiscal year (FY) 2022-23 Capital Improvement Program; and
b. Support the request to fund this project with funding from the Building Improvement and Replacement Sub-Fund (Fund 478-BIR, Appropriation Unit CAO047).
Report
RECOMMENDATION:
It is recommended that the Capital Improvement Committee:
a. Support a request to include the 1322 Natividad Road, Emergency Communications (911) Heating Ventilation and Air Conditioning Unit (HVAC) project into the fiscal year (FY) 2022-23 Capital Improvement Program; and
b. Support the request to fund this project with funding from the Building Improvement and Replacement Sub-Fund (Fund 478-BIR, Appropriation Unit CAO047).

SUMMARY/DISCUSSION:
In June 2022, three (3) of the four (4) compressors in the two (2) rooftop HVAC units failed at the 911 facility located at 1322 Natividad Road. As a result, Public Works, Facilities and Parks (PWFP) installed temporary compressor units to keep the equipment in the server room from overheating. Plumbing and heating contractors provided a service report with recommendations and costs to restore the use of the two (2) HVAC units. Upon review of the contractor's assessment, staff supports the contractor's recommendation to replace the two (2) HVAC units due to the following reasons:

* The HVAC units are 19 years old with a life expectancy of 20 years.
* Replacement parts are obsolete and difficult to obtain.
* The refrigerant in the units is difficult to find in California due to being outlawed in any new HVAC units.
* There will be no alarm function for the new compressors that require a new low-pressure switch. Without an alarm, the only notification of failure may be received by the server room equipment, which will start shutting down when overheated.
* The contractor can replace the two (2) compressors for approximatel...